HN 210D/X – HN214D/X RS-232 Serial Modbus Radio User’s Guide
HopNet RS-232 Serial ModBus Radio Getting Started A pair of HopNet radios are set up by performing the following steps: • Install the HopNet Wizard c
HopNet RS-232 Serial ModBus Radio Connect the other end of the serial cable to the DIN rail serial adapter box. Connect the end of the cable (RJ-45 c
HopNet RS-232 Serial ModBus Radio Click on the Continue button to bring up the next screen. The program will read and display the current settings o
HopNet RS-232 Serial ModBus Radio The Apply Settings button will appear at the bottom of the HopNet Configuration Wizard screen. Click on the Apply
HopNet RS-232 Serial ModBus Radio The Serial Adapter Box The HopNet radio remotes interface with the user’s hardware through a serial adapter box. Th
HopNet RS-232 Serial ModBus Radio Remote Pin-Out, RS-232 Pin Number Signal Type Description 1 DCD Output Data Carrier Detect. For remotes, DCD i
HopNet RS-232 Serial ModBus Radio Guidelines for Installation When installing your system, always consider the following points: Directional antennas
HopNet RS-232 Serial ModBus Radio Configuring the Network You can configure the HopNet network using a PC and the HopNet Configuration Wizard software
HopNet RS-232 Serial ModBus Radio NOTE: The S/N displayed in the bottom left corner is the serial number of the radio inside the unit and is different
HopNet RS-232 Serial ModBus Radio -40dBm=125 -95dBm=55 When the Wizard program is opened, it reads the parameters of the HopNet radio connected to the
Important Regulatory Information Cirronet Product FCC ID: HSW-2410 IC 4492A-2410 Note: This unit has been tested and found to comply with
HopNet RS-232 Serial ModBus Radio Depending on whether HopNet radio is configured as a Remote or Base when first connected, the heading on the Paramet
HopNet RS-232 Serial ModBus Radio Lockout Key This parameter is the same as wl and allows further network segregation beyond the network number. Thi
HopNet RS-232 Serial ModBus Radio When the radio is linked to another radio, a communications test can be run by clicking on the Send Data button (
HopNet RS-232 Serial ModBus Radio Network Tab Clicking on the Network tab will bring up a second configuration screen. From this screen it is possibl
HopNet RS-232 Serial ModBus Radio NOTE: The Transmit Delay is specified as a number of hop durations and thus will be an integer multiple of the Hop
HopNet RS-232 Serial ModBus Radio Set Hop Duration This is the ph command and it sets the length of time the transceiver spends on each frequency ch
HopNet RS-232 Serial ModBus Radio Protocol Tab The Protocol tab brings up the configuration screen above. On the next page are descriptions of the co
HopNet RS-232 Serial ModBus Radio Set the Frequency Operating Range (pe) by clicking on the drop-down menu and making a selection. ¹ Set Radio Powe
HopNet RS-232 Serial ModBus Radio RF Tools Clicking on the RF Tools tab brings up a screen that allows the receive signal strength to be monitored an
HopNet RS-232 Serial ModBus Radio Click on OK and the Select Connect Range screen will appear. Click on the estimated distance between radios and cli
Declaration of Conformity Warning! The RLAN transceiver within this device uses a band of frequencies that are not completely harmonized within th
HopNet RS-232 Serial ModBus Radio Receive and Bi-Directional Transmissions The Receive Only function displays the percentage success rate for recei
HopNet RS-232 Serial ModBus Radio The bars will change color depending on the level of the signal received. The points at which they change color hav
HopNet RS-232 Serial ModBus Radio WinCom Window Normally, the WinCom Window is not displayed and no tab will appear to the right of the RF Tools tab.
HopNet RS-232 Serial ModBus Radio NOTE: If the banner does not display, check the Banner Display Disable command (zb0) which may have been enabled.
HopNet RS-232 Serial ModBus Radio If an invalid command or value is entered, the radio will respond with “Error” as shown above Until the command to s
HopNet RS-232 Serial ModBus Radio The Clear Screen button deletes all the text in the display window. The Clear CTS and Clear DCD buttons reset the r
HopNet RS-232 Serial ModBus Radio Restart The Restart button on the Wizard causes the program to start the radio search and parameter load process aga
HopNet RS-232 Serial ModBus Radio message. If a reply is required, the controller will construct the reply message and send it using Modbus protocol.
HopNet RS-232 Serial ModBus Radio command or reply then verifies the BCC or CRC and returns an ACK—if the BCC or CRC is acceptable—or an NAK—if the BC
HopNet RS-232 Serial ModBus Radio entire packet to come in prior to transmission start using qd, the Maximum Transmit Delay (or Maximum Encapsulation
WARNING!! ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ For our Customers who wish to use this product in hazardous locations. The HN-210D, HN-210DX,
HopNet RS-232 Serial ModBus Radio European Union Operation When operating this product in the European Union, it is necessary to set the transmit powe
HopNet RS-232 Serial ModBus Radio Configuration Commands The HopNet radio has a wide selection of configuration parameters that can be modified using
HopNet RS-232 Serial ModBus Radio Serial Commands These commands affect the serial interface between the modem and the host. The default settings are
HopNet RS-232 Serial ModBus Radio Set Protocol Mode Enables the base station to operate in a multipoint network. Depending on the user application, m
HopNet RS-232 Serial ModBus Radio Network Commands Network commands are used to set up a HopNet network and to set radio addressing and configuration.
HopNet RS-232 Serial ModBus Radio Enable Global Network Mode For networks with multiple base stations, remotes are ordinarily only able to link to one
HopNet RS-232 Serial ModBus Radio Set Range Optimization This command applies an adjustment factor to the over-the-air timing of remotes to compensate
HopNet RS-232 Serial ModBus Radio Protocol Commands These commands can be used to tune the transceiver for optimum transmission of data across the RF
HopNet RS-232 Serial ModBus Radio Set Alternative Frequency Band When set to 1, limits the operating RF channel set to the 2448 to 2473MHz frequency
HopNet RS-232 Serial ModBus Radio Set Maximum Number of Remotes (base only) This parameter limits the number of remotes that can register with a given
Table of Contents Introduction ...1 Ho
HopNet RS-232 Serial ModBus Radio Set ARQ Mode This command sets ARQ mode when set to 0 which is the default. In this mode the radio will resend an u
HopNet RS-232 Serial ModBus Radio Set Escape Sequence Mode Enables or disables the ability to use the in-data-stream escape sequence method of access
HopNet RS-232 Serial ModBus Radio Memory Commands The user is able to store a configuration in nonvolatile memory, which is loaded during the initiali
HopNet RS-232 Serial ModBus Radio Adapter Commands The following commands are available via WinCom24. Command Description qp[?|0|1|2] Protocol Mod
HopNet RS-232 Serial ModBus Radio Modem Command Summary Serial Commands sd[?|00..ff] Set Data Rate Divisor sp[?|00..14] Set Protocol Mode Network
HopNet RS-232 Serial ModBus Radio Troubleshooting Overview Introduction Troubleshooting the HopNet products is not difficult, but it does require a lo
HopNet RS-232 Serial ModBus Radio Common System Problems The following table offers suggestions for resolving some common system problems that the ope
HopNet RS-232 Serial ModBus Radio Guidelines for Reducing Interference Introduction The transceivers share the same frequency spectrum with other serv
HopNet RS-232 Serial ModBus Radio Guidelines for Avoiding Terrain Obstructions The HopNet transceivers operate in the 2.4 GHz frequency band. While th
HopNet RS-232 Serial ModBus Radio Customer Support Introduction Cirronet, Inc. products are designed for long life and trouble free operation. The fol
Troubleshooting ...49 Overview...
HopNet RS-232 Serial ModBus Radio Technical Specifications Refer to the tables below for the technical specifications for the HopNet radio Remotes. El
HopNet RS-232 Serial ModBus Radio Mechanical Specification Value Case NEMA 4X, IP 66 Size 5.1 in. x 3.1 in. x 1.4 in. 130mm x 80mm x 35mm Weight
HopNet RS-232 Serial ModBus Radio Glossary of Terms Refer to the following list of terms that may be unfamiliar to you. These terms are used throughou
HopNet RS-232 Serial ModBus Radio ISM Industrial, Scientific, or Medical band operating at 2.4 GHz. Allows use of a radio without a license, but the
HopNet RS-232 Serial ModBus Radio Warranty Seller warrants solely to Buyer that the goods delivered hereunder shall be free from defects in materials
HopNet RS-232 Serial ModBus Radio Introduction The HopNet family of products provides reliable wireless connectivity for either point-to-point or poin
HopNet RS-232 Serial ModBus Radio Frequency Hopping Spread Spectrum reduces the vulnerability of a radio system to interference from jammers and multi
HopNet RS-232 Serial ModBus Radio Advanced Features HopNet modems have many advanced features: • Employ frequency hopping technology with up to 75 ch